N120

Single-board OEM process controller

Controller for building into equipment with universal input, adaptive PID and ramp & soak control – optionally with data logger.

  • Thermocouple, Pt100, mA, mV and V input
  • SSR pulse output + 2 × relay, digital input
  • 20 programs with 9 segments, 4 alarms with timers
  • USB and RS-485 Modbus RTU, dimensions 100 × 67 × 28 mm
  Request an individual quote
N120

N120

Single-board OEM process controller

Controller for building into equipment with universal input, adaptive PID and ramp & soak control – optionally with data logger.

  • Thermocouple, Pt100, mA, mV and V input
  • SSR pulse output + 2 × relay, digital input
  • 20 programs with 9 segments, 4 alarms with timers
  • USB and RS-485 Modbus RTU, dimensions 100 × 67 × 28 mm

I accept privacy policy  

 

Single-board OEM process controller with program control: NOVUS N120

The NOVUS N120 is an advanced single-board OEM self-adaptive process controller with an optional data logger. It is designed for machine and equipment manufacturers who build it directly into their product – for example an oven, dryer or laboratory instrument. Its dimensions of 100 × 67 × 28 mm allow installation even in a small space.

The universal measuring input accepts all common thermocouples, Pt100 and industrial current and voltage signals. The N120 has one voltage pulse output for controlling a solid-state relay (SSR) and two relays; each output can be set for control, alarm, diagnostics or program status signalling. Two control outputs allow simultaneous heating and cooling control. A digital input is used to operate selected functions, USB for configuration and data download, and RS-485 (Modbus RTU) for field data acquisition and connection to SCADA systems.

Parameter tuning offers several algorithms – fast (FAST), precise (FULL) and adaptive (SELF) with automatic start. The N120 is ideal for program (ramp and soak) control: it has 20 programs with 9 segments each, which can be linked or repeated endlessly. Four alarms are complemented by timer functions – an alarm can last for a limited time, be delayed or pulse cyclically. The data logger model stores up to 32,000 time-stamped records.


Benefits of the NOVUS N120 controller

  • OEM design: single-board controller 100 × 67 × 28 mm for building into equipment.
  • Universal input: J, K, T, N, R, S, B, E thermocouples, Pt100, 0/4–20 mA, 0–50 mV, 0–5 V and 0–10 V.
  • Adaptive PID control: FAST, FULL and SELF auto-tuning, heating and cooling, auto and manual mode.
  • Program control: 20 programs with 9 segments, linking and repetition, hold when the process lags behind.
  • 4 alarms with timers: limited duration, delay or cyclic pulses, sensor and loop diagnostics.
  • Data logger: up to 32,000 records with real-time clock in the -DL model.
  • USB and RS-485 Modbus RTU: as standard, with free QuickTune and FieldChart-Lite software.
  • Fast measurement: up to 55 measurements per second, 15-bit resolution.

Technical specifications

Parameter Value
Design single-board OEM controller for building into equipment
Dimensions (W × H × D) 100 × 67 × 28 mm
Measuring input universal: thermocouples J, K, T, N, R, S, B, E; Pt100 (3-wire); 0–20 mA, 4–20 mA, 0–50 mV, 0–5 V, 0–10 V
Measuring range Pt100: −200 to +850 °C; J: −110 to +950 °C; K: −150 to +1370 °C; T: −160 to +400 °C; N: −270 to +1300 °C; R, S: −50 to +1760 °C; B: +400 to +1800 °C; E: −90 to +730 °C; analogue signals: −1999 to 9999 (scalable)
Accuracy J, K, T, E thermocouples 0.25 % of span ±1 °C; N, R, S, B 0.25 % of span ±3 °C; Pt100 and analogue signals 0.2 % of span
Resolution / sampling rate 15 bits, up to 55 measurements per second
Input impedance thermocouples, Pt100, 0–50 mV > 10 MΩ; 0–5 V > 1 MΩ; 4–20 mA 15 Ω
Output OUT1 voltage pulse 5 V, max. 20 mA (for SSR control)
Outputs OUT2, OUT3 relay, SPST, max. 250 V AC, 3 A (resistive load)
Output functions control, alarm, diagnostics or program status signalling
Digital input control or program run/stop, auto/manual mode, local/remote setpoint, program hold, program 1 selection
Control ON/OFF, three-position or PID with 1 or 2 outputs (heating, cooling or heating + cooling with overlap or dead band); auto/manual mode; soft start 0 to 9999 s
PID auto-tuning fast (FAST), precise (FULL), adaptive control (SELF) and their combinations with automatic start
Program control 20 programs with 9 segments each, program linking (LP) and endless repetition; segment 1 to 9999 minutes or seconds; automatic hold when the process lags behind (PTOL)
Alarms up to 4 process alarms (HI, LO, DIFH, DIFL, DIF) + sensor break and loop break (LBD) detection; alarm timers – single pulse, delayed activation or pulse train 1 to 6500 s
Data logger (-DL model) up to 32,000 records in battery-backed memory with real-time clock
Communication USB (configuration, data download) and RS-485, Modbus RTU (field data acquisition, SCADA)
Software QuickTune (configuration, diagnostics) and FieldChart-Lite (data logging) free of charge; FieldChart-64C, SuperView SCADA
Security numeric password with time lock, 7 levels of parameter protection
Power supply 100–240 V AC/DC (±10 %), 50/60 Hz
Consumption max. 5 VA
Operating conditions 5 to 60 °C, up to 80 % relative humidity, max. altitude 2000 m

Model overview

Order code Description
N120-PRR-485 basic model: SSR pulse output + 2 × relay, digital input, USB, RS-485
N120-PRR-485-DL as basic model + data logger with real-time clock

Where the N120 is used

The N120 controller is used mainly by machine and equipment manufacturers (OEM) – in industrial and laboratory ovens and furnaces, dryers, autoclaves, heat treatment equipment, food and plastics processing machines, and wherever program control of temperature or other process variables is needed directly inside the equipment. As a sensor you can use, for example, our easytherm ET10 cable sensor with Pt100 or thermocouple.

Need help choosing the right controller or sensor? Contact our technical team. Find more controllers in the Controllers category.

Measuring sensor
0–5 V
0–10 V
0–20 mA
0–50 mV
4–20 mA
Pt100
thermocouple B
thermocouple E
thermocouple J
thermocouple K
thermocouple N
thermocouple R
thermocouple S
thermocouple T
Number of measuring inputs
1
Control output
pulse (for SSR control)
relay
Alarm
more than 2
Digital input
1
Industrial communication
RS-485
USB
Display
Yes
Mounting
OEM board for built-in mounting
Application
Advanced PID control + autotuning
Constant temperature control
Heating + cooling control (reverse + direct action)
On/off control
PID control + autotuning
Program control
Ramp (ramp + soak)
N120