N1050

PID controller with program control and timer

48 × 48 mm controller with LCD display, 5 programs with 4 segments, timer and USB – optionally with RS-485 Modbus.

  • Pt100 or J, K, T, S thermocouple input (up to +1760 °C)
  • Pulse output for SSR + 1 or 3 relays
  • Ramp & soak program control, 2 timers, 2 alarms
  • Power supply 100–240 V AC / 48–240 V DC or 12–24 V
  Request an individual quote
N1050

N1050

PID controller with program control and timer

48 × 48 mm controller with LCD display, 5 programs with 4 segments, timer and USB – optionally with RS-485 Modbus.

  • Pt100 or J, K, T, S thermocouple input (up to +1760 °C)
  • Pulse output for SSR + 1 or 3 relays
  • Ramp & soak program control, 2 timers, 2 alarms
  • Power supply 100–240 V AC / 48–240 V DC or 12–24 V

I accept privacy policy  

 

PID temperature controller with program control and LCD display: NOVUS N1050

The NOVUS N1050 is an affordable and simple temperature controller with proven PID algorithms which, thanks to its clear LCD display, program control and timer, reaches into a higher class. The operator menu can be customised to contain only the functions that are actually used.

A Pt100 resistance sensor or a type J, K, T or S thermocouple can be connected to the measuring input. The N1050 has one voltage pulse output for controlling a solid-state relay (SSR) and 1 or 3 relays, which can be assigned to control, alarms, diagnostics, program status signalling or timers. The controller has a USB connector for configuration and data logging in the lab and optionally an RS-485 (Modbus RTU) serial bus for data acquisition in the field and connection to SCADA systems. An installation depth of 70 mm and a removable terminal block make installation and replacement easy.

The N1050 is ideal for program (ramp and soak) control. It has 5 programs with 4 segments each, which can be linked together or repeated endlessly. Each segment contains the target setpoint, the time to reach it and the state of the signalling outputs – a soak at the same temperature is programmed simply by using the same value as in the previous segment. During the program, the display shows the segment number and remaining time. Two timers from 00:00 to 99:59 allow simple time-limited processes to be controlled and signalled as well.


Benefits of the NOVUS N1050 controller

  • Program control: 5 programs with 4 segments, program linking and repetition, power failure handling.
  • Timer: two timers up to 99:59 for controlling and signalling the end of the process.
  • LCD display: easy to read, with a customisable operator menu.
  • Wide measuring input: Pt100, J, K, T and S thermocouples up to +1760 °C.
  • Up to 4 outputs: pulse for SSR + 1 or 3 relays for control, alarms, program signalling or timers.
  • USB and RS-485: USB as standard, optional RS-485 Modbus RTU; free QuickTune and FieldChart-Lite software.
  • PID with auto-tuning: fast or precise tuning, soft start, sensor and control loop diagnostics.
  • Compact format: 1/16 DIN (48 × 48 mm), IP65 front panel, CE, UL and cUL approvals.

Technical specifications

Parameter Value
Front panel format 1/16 DIN, 48 × 48 mm
Depth / installation depth 80 mm / 70 mm
Panel cut-out 46 × 46 mm
Display LCD, easy to read
Measuring input Pt100 (3-wire), thermocouple J, K, T or S
Measuring range Pt100: −200 to +850 °C; J: −110 to +950 °C; K: −150 to +1370 °C; T: −160 to +400 °C; S: −50 to +1760 °C
Accuracy J, K, T thermocouples 0.25 % of span ±1 °C; S thermocouple 0.25 % of span ±3 °C; Pt100 0.2 % of span
Resolution / sampling rate 15 bits, 10 measurements per second (without filtering), otherwise 5 per second
Input impedance > 10 MΩ; Pt100 excitation current 0.170 mA
Output 1 voltage pulse 5 V DC, max. 25 mA (for SSR control)
Outputs 2 and 3 (depending on model) relay, SPST, max. 240 V AC / 30 V DC, 1.5 A (resistive load)
Output 4 (depending on model) relay, SPDT, max. 240 V AC / 30 V DC, 3 A (resistive load)
Output functions control, alarms, diagnostics, program status signalling, timers
Control ON/OFF or PID; heating (reverse action) or cooling (direct action); soft start 0 to 9999 s
PID auto-tuning fast (FAST) or precise (FULL)
Program control 5 programs with 4 segments each, program linking (LP) and endless repetition; segment 00:01 to 99:59 (hh:mm or mm:ss)
Program operation start/stop, hold/resume; automatic hold when the process lags behind (PTOL)
Power failure handling return to program start, resume from the start of the segment or from the point of failure, or end the program
Alarms up to 2 process alarms (HI, LO, DIFH, DIFL, DIF) + sensor break and loop break (LBD) detection
Timer 2 timers T1 and T2, 00:00 to 99:59 (hh:mm or mm:ss); start by reaching the setpoint, RUN function or key
Communication USB (configuration, data logging in the lab); optional RS-485, Modbus RTU Slave (data acquisition in the field, SCADA)
Software QuickTune (configuration, diagnostics) and FieldChart-Lite (data logging) free of charge; FieldChart-64C, SuperView SCADA
Security numeric password with time lock, 8 levels of parameter protection
Power supply 100–240 V AC (±10 %), 50/60 Hz or 48–240 V DC; 24V model: 12–24 V DC / 24 V AC
Consumption max. 6 VA
Operating conditions 0 to 50 °C, up to 80 % relative humidity, max. altitude 2000 m
Protection front panel IP65, terminals IP30
Connection removable screw terminal block
Approvals CE, UL, cUL

Model overview

Order code Outputs RS-485 Power supply
N1050-PR SSR pulse + relay – 100–240 V AC / 48–240 V DC
N1050-PR-24V SSR pulse + relay – 12–24 V DC / 24 V AC
N1050-PRRR-485 SSR pulse + 3 × relay yes 100–240 V AC / 48–240 V DC
N1050-PRRR-485-24V SSR pulse + 3 × relay yes 12–24 V DC / 24 V AC

All models have USB.


Where the N1050 is used

The N1050 controller is used wherever temperature changes according to a time profile – in laboratory and industrial ovens and furnaces, heat treatment, ceramic firing, drying, curing and tempering, in the food industry and in plastics processing. With the S thermocouple input it also handles high-temperature furnaces up to +1760 °C. As a sensor you can use, for example, our easytherm ET10 cable sensor with Pt100 or thermocouple.

Need help choosing the right model or temperature sensor? Contact our technical team. Find more controllers in the Controllers category.

Format
1/16 DIN
Measuring sensor
Pt100
thermocouple J
thermocouple K
thermocouple S
thermocouple T
Number of measuring inputs
1
Control output
pulse (for SSR control)
relay
Alarm
2
Timer
Yes
Industrial communication
RS-485
USB
Display
Yes
Mounting
Panel cutout
Application
Constant temperature control
Heating + cooling control (reverse + direct action)
On/off control
PID control + autotuning
Program control
Ramp (ramp + soak)
N1050