Fuji FKC – differential pressure transmitter (FCX-AIV series)
Fuji Electric FKC accurately measures differential pressure, liquid level or flow rate and converts it into a 4–20 mA output signal with HART communication. It is designed for demanding applications in the process industry.
- High accuracy: ±0.065% of span, optionally ±0.04%.
- Wide ranges: from 1 kPa to 20 MPa, static pressure up to 42 MPa.
- Functional safety: SIL 2 (HFT=0) and SIL 3 (HFT=1) according to IEC 61508 and IEC 61511.
- Communication: HART 7, zero and span adjustment also directly on the device.
Accurate measurement of differential pressure, flow and level: Fuji Electric FKC transmitter
The Fuji Electric FKC differential pressure transmitter from the FCX-AIV series accurately measures differential pressure, liquid level or flow rate and converts it into a proportional 4–20 mA output signal. At the heart of the measuring element is a micro-capacitive silicon sensor which, combined with digital signal processing, ensures excellent accuracy and long-term stability.
The Advanced Floating Cell technology greatly reduces the influence of temperature variations, static pressure and overpressure commonly found in the process industry. The FCX-AIV series meets safety integrity levels SIL 2 (HFT=0) and SIL 3 (HFT=1) according to IEC 61508 and IEC 61511, making it suitable for safety loops as well.
Key benefits and features of the Fuji FKC
- High accuracy: ±0.065% of set span, optionally up to ±0.04%.
- Wide measuring ranges: maximum ranges of 1, 6, 32, 130, 500, 3,000 and 20,000 kPa, with a turndown of up to 100:1.
- High static pressure: up to 42 MPa (420 bar) depending on model.
- Flow measurement: square root output with adjustable low flow cut-off.
- Output linearization: up to 14 points, e.g. for volume measurement in irregular tanks.
- Long-term stability: ±0.1% of upper range limit over 10 years.
- Resistant materials: diaphragm made of 316L stainless steel, Hastelloy C, Monel, tantalum or gold-plated 316L.
- HART 7 communication: remote configuration and diagnostics.
- Functional safety: SIL 2 / SIL 3 according to IEC 61508 and IEC 61511.
Technical specifications
| Parameter | Value |
|---|---|
| Measured variable | differential pressure, level, flow |
| Maximum measuring ranges | 1 / 6 / 32 / 130 / 500 / 3,000 / 20,000 kPa |
| Maximum static pressure | 3.2 / 10 / 16 / 30 / 42 MPa (depending on model) |
| Span adjustment range | down to 1/100 of maximum range |
| Zero elevation / suppression | −100 to +100% of maximum range |
| Accuracy | ±0.065% of set span (optionally ±0.04%); 1 kPa, 6 kPa and 20 MPa models: ±0.1% |
| Stability | ±0.1% of upper range limit / 10 years |
| Measuring cycle | 40 ms |
| Damping | adjustable 0.04 to 32 s |
| Output signal | 4–20 mA DC, linear or square root (min. 250 Ω load for HART) |
| Communication | HART 7 |
| Power supply | 10.5 to 45 V DC (loop powered) |
| Process temperature | −40 to +120 °C (silicone oil), −20 to +80 °C (fluorinated oil) |
| Ambient temperature | −40 to +85 °C (with indicator −20 to +80 °C) |
| Diaphragm material | 316L stainless steel, Hastelloy C, gold-plated 316L stainless steel, Monel, tantalum |
| Process covers | 316L stainless steel |
| Filling fluid | silicone oil, optionally fluorinated oil |
| Housing | L or T shape, low-copper aluminium alloy with polyester coating, or 316 stainless steel |
| Electrical connection | M20 × 1.5 / 1/2" – 14 NPT / Pg13.5 |
| Process connection | 1/4"-18 NPT according to DIN 19213, optionally 1/2"-14 NPT with oval flanges |
| Protection | IP66 / IP67 |
| Hazardous area (optional) | ATEX / IECEx – intrinsic safety (Ex ia) or flameproof (Ex d) |
| Weight | approx. 3.5 kg (without options) |
| Functional safety | SIL 2 (HFT=0), SIL 3 (HFT=1) according to IEC 61508 / IEC 61511 |
Options and accessories
- 5-digit digital indicator, optionally with local configuration via magnetic buttons
- ATEX / IECEx hazardous area versions
- surge protection (lightning arrester)
- stainless steel housing
- oxygen and chlorine service, degreasing of wetted parts
- NACE MR0175 / ISO 15156 compliant version
- 316L stainless steel manifolds rated 16 MPa or 42 MPa
- additional stainless steel identification tag
Where the FKC is used
The FKC transmitter is used for flow measurement of liquids, gases and steam with orifice plates and other primary elements, level measurement in closed tanks, density and interface measurement, and filter clogging monitoring. It is widely used in the chemical, petrochemical and pharmaceutical industries, in the energy sector, water treatment and food production.
Need help choosing the right range, material or connection? Contact our technical team. Find more transmitters in the Pressure sensors and switches category.
- Industrial communication
- HART
- Display
- optional
- Pressure type
- differential
- Measuring range
- 1 – 10 MPa
100 kPa – 1 MPa
above 10 MPa
up to 100 kPa - Output signal
- 4–20 mA
- Accuracy
- ±0,04 %
±0,065 %
±0,1 % - Diaphragm material
- 316L stainless steel
Hastelloy C
Monel
gold-plated 316L
tantalum - Functional safety
- SIL 2
SIL 3 - Power supply
- loop powered
- Protection
- IP66/IP67
- Device type
- pressure transmitter
- Medium
- gases
liquids
steam - Process connection
- 1/2" NPT
1/4" NPT - Electrical connection
- 1/2" NPT
Pg13,5
cable gland M20 × 1.5 - Approvals
- ATEX
IECEx