Clamp-on ultrasonic flow meter for saturated steam
Measures steam flow from outside on DN50 to DN100 pipes – without cutting the pipe, without shutdown and without risk of steam leaks.
- Pressure 0.1–0.9 MPa, temperature up to +180 °C, measurement from zero flow
- Mass flow conversion (kg/h) via pressure, temperature or Pt100 input
- 4–20 mA, 2 × pulse/alarm outputs, optional RS-485 Modbus
- IP67 transmitter, power supply 100–240 V AC
Clamp-on ultrasonic steam flow meter: Fuji Electric FSJ
The Fuji Electric FSJ is a clamp-on ultrasonic flow meter for measuring the flow of saturated steam. The FSX detectors are fixed from outside onto a DN50 to DN100 steam pipe, so no pipe cutting, welding or production shutdown is needed – and there is no risk of steam leakage. The measurement has no moving parts, causes no pressure loss and is not damaged by water hammer.
Conventional clamp-on flow meters cannot measure steam. The FSJ can, thanks to high-sensitivity ultrasonic sensors and noise reduction technology, in a pressure range of 0.1 to 0.9 MPa and at temperatures up to +180 °C. It measures from zero flow, which most steam flow meters cannot do, and uses a pressure or temperature input to convert volumetric flow into mass flow in kg/h. It has a 4–20 mA output, two digital outputs and optional RS-485 Modbus communication.
Benefits of the Fuji FSJ flow meter
- No intervention in the steam pipe: installation during operation, without cutting, welding or risk of steam leaks.
- Zero pressure loss and no moving parts – minimal maintenance, resistance to water hammer.
- Measurement from zero: captures even very low flows and steam leaks.
- Mass flow: conversion using a fixed density, a 4–20 mA pressure / temperature input or a Pt100 sensor.
- Fast 0.2 s response and bi-directional measurement.
- Self-diagnostics: received signal and signal-to-noise ratio checks, dialogue troubleshooting, remote diagnostics via RS-485.
- Rugged design: aluminium transmitter with IP67 protection, ambient temperature −20 to +60 °C.
Measuring ranges
| Size | Outer diameter | Max. velocity | Max. volumetric flow | Max. mass flow at 0.1 / 0.5 / 0.9 MPa | Steam pressure | Steam temperature |
|---|---|---|---|---|---|---|
| DN50 | 60.5 mm | ±50 m/s | 396 m³/h | 450 / 1256 / 2037 kg/h | 0.1 – 0.9 MPa | +120 to +180 °C |
| DN65 | 76.3 mm | ±50 m/s | 652 m³/h | – / 2069 / 3357 kg/h | 0.2 – 0.9 MPa | +134 to +180 °C |
| DN80 | 89.1 mm | ±50 m/s | 921 m³/h | – / 2923 / 4741 kg/h | 0.2 – 0.9 MPa | +134 to +180 °C |
| DN100 | 114.3 mm | ±30 m/s | 941 m³/h | – / 2986 / 4844 kg/h | 0.2 – 0.9 MPa | +134 to +180 °C |
Pressure is gauge pressure. Values apply to SGP steel pipes; the actual range depends on the pipe inner diameter. The lower limit of measurement is 0 m/s.
Accuracy
| Flow velocity | DN50 | DN65, DN80, DN100 |
|---|---|---|
| 0 – 10 m/s | ±0.3 m/s | ±0.4 m/s |
| 10 – 30 m/s | ±3% of rate | ±4% of rate |
| 30 – 50 m/s | ±5% of rate | ±5% of rate (DN100 only up to 30 m/s) |
Applies to the displayed value and pulse output; for the analogue output, ±0.04 mA is added. Accuracy depends on the condition of the steam, the piping and the length of straight runs.
Technical specifications
| Parameter | Value |
|---|---|
| Measuring principle | ultrasonic, transit time difference, clamp-on detectors |
| System | FSJ flow transmitter, FSX detector with pre-amplifier, FLYE dedicated cable |
| Measured medium | saturated steam with 0% wetness, no entrained water; not superheated steam |
| Piping | DN50, DN65, DN80, DN100; steel or stainless steel; wall thickness 2.8 to 4.5 mm; lined pipes not supported |
| Straight pipe runs | min. 20 × D upstream and 10 × D downstream (after a bend), more after fittings and pumps |
| Response time | 0.2 s; approx. 10 min for the detector temperature to stabilise after steam starts to flow |
| Analogue output | 4–20 mA DC, isolated, load max. 600 Ω – volumetric or mass flow |
| Digital outputs | 2 × transistor (open collector, isolated) 30 V DC / 50 mA, max. 100 pulses/s – total pulses, alarm, flow switch and total switch, flow direction |
| Analogue input | 4–20 mA DC, isolated – saturated steam pressure or temperature for mass flow conversion |
| Temperature input (optional) | Pt100 – steam or pipe surface temperature, range 100 to 180 °C (Pt100 sensor ordered separately) |
| Communication (optional) | RS-485 Modbus, isolated, up to 31 instruments, 9,600 to 38,400 bps, cable up to 1 km |
| Display | backlit LCD 2 × 16 characters, two-colour status LED; velocity, volumetric and mass flow, total (9 digits); menu in English, German, French, Spanish and Japanese |
| Functions | damping 0 to 100 s, low flow cut-off, bi-directional measurement, auto 2-range switching, configurable burnout, backup in non-volatile memory |
| Power supply | 100 to 240 V AC, 50/60 Hz, max. 20 VA; surge protection on power supply and analogue output |
| Protection | IP67 (with connectors fitted) |
| Environment | −20 to +60 °C, max. 95% RH, vibration 0.5 G (5 to 200 Hz); non-hazardous areas |
| Materials | transmitter aluminium alloy with urethane coating; detector plastic and stainless steel; detector bracket aluminium and stainless steel; noise elimination frame heat-resistant rubber and stainless steel |
| Weight | transmitter 5.5 kg; detector 6.5 kg (DN50), 7.5 kg (DN65), 8.0 kg (DN80), 8.5 kg (DN100); pre-amplifier 1.5 kg |
| Cables | detector – pre-amplifier 2 m; pre-amplifier – transmitter FLYE 5 to 30 m, Ø 11.5 mm |
| Transmitter mounting | wall or pipe mounting; watertight cable glands G1/2 and G3/8 or conduit connection |
| Compliance | CE – LVD (EN 61010-1), EMC (EN 61326-1, EN 61326-2-3, EN 55011), RoHS |
Options and accessories
- Fuji FSX detector for DN50, DN65, DN80 or DN100 including pre-amplifier, bracket and noise elimination frames
- FLYE dedicated cable in lengths of 5, 10, 15, 20, 25 or 30 m
- KS-62M high-temperature grease (short-term installation, approx. 6 months) or grease for long-term installation (approx. 2 years)
- RS-485 Modbus communication and Pt100 input
- wall or pipe mounting of the transmitter, factory parameter setting and tag plate
- PC software for configuration and data logging included
After installation, the detector is insulated together with the pipe; the pre-amplifier is not insulated.
Where the FSJ is used
The FSJ flow meter is used to measure steam consumption in district heating, in the metals industry, in the paper industry, in the food and pharmaceutical industries (sterilisation, CIP cleaning), on boiler auxiliaries (air preheaters, heat exchangers) and wherever steam consumption needs to be allocated to individual lines, steam leaks detected and steam generation and distribution optimised – without intervention in the steam network.
For measuring liquid flow, the Fuji Time Delta-C FSV clamp-on flow meter is available.
Need help designing a steam measurement? Contact our technical team. Find more flow meters in the Flow & Level Measurement category.
- Display
- Yes
- Output signal
- 4–20 mA
Modbus
pulse - Accuracy
- ±3 %
- Power supply
- 100–240 V AC
- Protection
- IP67
- Device type
- flow meter
- Medium
- steam
- Process connection
- clamp-on
- Measuring principle
- ultrasonic
- Nominal diameter
- DN50 – DN100
- Input signal
- Pt100