Fuji FKR – high pressure transmitter up to 700 bar (FCX-AIV series)
Fuji Electric FKR accurately measures gauge pressure up to 70 MPa and converts it into a 4–20 mA output signal with HART communication. It is designed for extreme conditions – hydrogen, hydraulics, high pressure processes and test benches.
- High accuracy: ±0.065% of set span.
- High pressure: range up to 700 bar, overrange limit 1,050 bar.
- Durable materials: Inconel 625 diaphragm, F250C autoclave connection.
- Functional safety: SIL 2 (HFT=0) and SIL 3 (HFT=1) according to IEC 61508 and IEC 61511.
Accurate measurement of very high pressures: Fuji Electric FKR transmitter up to 700 bar
The Fuji Electric FKR high pressure transmitter from the FCX-AIV series accurately measures gauge pressure up to 70 MPa (700 bar) and converts it into a proportional 4–20 mA output signal with HART 7 communication. At the heart of the measuring element is a piezoresistive silicon sensor which, combined with digital signal processing, provides high accuracy and long-term stability.
The Inconel 625 nickel alloy diaphragm and the process connection in duplex stainless steel 318LN or Inconel 625 are designed for extreme conditions. The transmitter mounts directly on the pipe via an F250C autoclave connection. The FCX-AIV series meets safety integrity levels SIL 2 (HFT=0) and SIL 3 (HFT=1) according to IEC 61508 and IEC 61511.
Key benefits and features of the Fuji FKR
- High pressure: measuring range up to 70 MPa (700 bar), overrange limit up to 105 MPa (1,050 bar).
- High accuracy: ±0.065% of set span.
- Durable materials: Inconel 625 diaphragm, optionally gold-plated, process connection in 318LN (duplex) steel or Inconel 625.
- Autoclave connection: F250C female thread, with adapter F250C male thread or 1/4"-18 NPT.
- Compact design: weight only 1.5 kg (aluminium housing).
- Fast response: 40 ms measuring cycle, response time approx. 140 ms.
- Long-term stability: ±0.1% of upper range limit over 5 years.
- HART 7 communication: remote configuration and diagnostics, burnout current according to NAMUR NE43, configuration without opening the cover via magnetic buttons.
- Functional safety: SIL 2 / SIL 3 according to IEC 61508 and IEC 61511.
Technical specifications
| Parameter | Value |
|---|---|
| Measured variable | gauge pressure |
| Maximum measuring range | 70 MPa (700 bar) |
| Span adjustment range | 4.375 to 70 MPa (down to 1/16 of maximum range) |
| Range limits | −0.1 to +70 MPa |
| Overrange limit | 105 MPa (1,050 bar) |
| Accuracy | ±0.065% of set span (for spans greater than 1/10 of upper range limit) |
| Stability | ±0.1% of upper range limit / 5 years |
| Measuring cycle | 40 ms |
| Response time | time constant 80 ms + dead time approx. 60 ms |
| Damping | adjustable 0.04 to 32 s |
| Output signal | 4–20 mA DC, linear or square root, up to 14-point linearization (min. 250 Ω load for HART) |
| Communication | HART 7 |
| Power supply | 10.5 to 45 V DC (loop powered), 10.5 to 32 V DC with arrester |
| Process temperature | −40 to +100 °C (silicone oil) |
| Ambient temperature | −40 to +85 °C (with indicator −20 to +80 °C) |
| Process connection | F250C autoclave female thread; with adapter F250C male thread or 1/4"-18 NPT female thread |
| Diaphragm material | Inconel 625 (Alloy 625), optionally gold-plated |
| Process connection material | duplex stainless steel 318LN (1.4462) or Inconel 625 |
| Sensor body material | 316L stainless steel or Inconel 625 |
| Filling fluid | silicone oil or mineral oil |
| Housing | L or T shape, low copper die-cast aluminium with polyester coating, or 316L stainless steel |
| Electrical connection | M20 × 1.5 / 1/2" – 14 NPT / Pg13.5 |
| Protection | IP66 / IP67, NEMA 4X |
| Hazardous area (optional) | ATEX / IECEx / cCSAus – intrinsic safety (Ex ia) or flameproof (Ex d) |
| Weight | 1.5 kg (aluminium housing), approx. 3 kg (stainless steel housing) |
| Functional safety | SIL 2 (HFT=0), SIL 3 (HFT=1) according to IEC 61508 / IEC 61511 |
Options and accessories
- 5-digit digital indicator, optionally with local configuration via magnetic buttons
- ATEX / IECEx / cCSAus hazardous area versions
- surge protection (lightning arrester)
- 316L stainless steel housing
- gold-plated diaphragm
- NACE MR0175 / ISO 15156 compliant version, degreasing
- stainless steel mounting bracket for 50 mm (2") pipe
- additional stainless steel identification tag
Where the FKR is used
The FKR transmitter is designed to measure very high pressures in demanding industrial applications – hydrogen production and distribution, hydraulic presses and plastic injection moulding machines, supercritical steam, hydrotreating and hydrocracking processes, subsea valve control, high-pressure cryogenics, CO₂ storage and distribution, nuclear power and test benches.
Need help choosing the right range, material or connection? Contact our technical team. Find more transmitters in the Pressure sensors and switches category.
- Industrial communication
- HART
- Display
- optional
- Pressure type
- gauge
- Measuring range
- 1 – 10 MPa
above 10 MPa - Output signal
- 4–20 mA
- Accuracy
- ±0,065 %
- Diaphragm material
- Inconel 625
gold-plated Inconel 625 - Functional safety
- SIL 2
SIL 3 - Power supply
- loop powered
- Protection
- IP66/IP67
- Device type
- pressure transmitter
- Medium
- gases
hydrogen
liquids - Process connection
- 1/4" NPT
autoclave UNF - Electrical connection
- 1/2" NPT
Pg13,5
cable gland M20 × 1.5 - Approvals
- ATEX
IECEx